HARDO motor switch

Motor switches

circuit-breakers-motor-Ex-do-zone-explosion-hardo


Interchangeable with switches from leading manufacturers:

Designed for Ex zones: 1, 2, 21, 22

Five protections (overload, short-circuit, thermal, phase loss, undervoltage – optional)

The overload protection follows tripping characteristics comparable to those used by leading manufacturers.

Large dial ⌀ 97 mm, for easy operation with gloves

LOTO locking option (three padlocks)

Download


Technical data:

Dimensions: please see details below

Certifications: ATEX, IECEx

ATEX designation:

II 2 G Ex db eb IIC T4/T5/T6 Gb
II 2 G Ex db eb IIC T4/T5/T6 Gb
II 2 D Ex tb IIIC T85oCDb

IECEx designation:

Ex db eb IIC T5/T6 Gb
Ex tb IIIC T85oCDb

Housing material: GRP

Knob size: Ø 97 mm

Permissible ambient temperature: -40°C to +55°C

Degree of protection: IP66

Rated voltage: 440 V

Protections applied: overload; phase loss; short circuit; thermal; undervoltage (optional);

Overload trip setting range: 0.1 to 25 A

Switching capacity of motor in AC3 category: up to 440 V / 25 A

Main contacts: 1 – 10 mm² (6 – 10 mm² using collets)

Auxiliary contacts: 1 – 2.5 mm²

Auxiliary contact capacity: AC15 1 A / 230 V

Rated switching capacity: high (up to 65 kA)


Price:

Large knob
Operable with gloves
Front dimensions
Side dimensions

5 types of security – 100% as offered by major market players

01/ OVERLOAD

02/ SHORT-CIRCUIT PROTECTION

03/ THERMAL

04/ PHASE LOSS

05/ UNDERVOLTAGE (optional)


Overload protection

The motor circuit breakers for hazardous areas have built-in overload protection, which protects the motor not only against long-term overload, but also against frequent restarts or brief overloads that can lead to overheating of the windings. The motor circuit breakers are available with adjustable overload protection in the 0.1–25 A range. The unit is rated for 440 V operation.

Setting ranges (0.1 – 25 A)

The pre-setting of the appropriate trip current value takes place at the production stage, according to the customer’s requirements and the application of the circuit breaker in question. It is also possible to adjust the range directly on site.

For values of the overload ranges, see table below.

Overload trip setting range
Rated switching and breaking capacity
Cable glands
Part number

0.1 – 0.16 A

65 kA

2 x M25

HCS1P 252616 S01211

0.16 – 0.25 A

65 kA

2 x M25

HCS1P 252616 S01221

0.25 – 0.4 A

65 kA

2 x M25

HCS1P 252616 S01231

0.4 – 0.63 A

65 kA

2 x M25

HCS1P 252616 S01241

0.63 – 1 A

65 kA

2 x M25

HCS1P 252616 S01251

1 – 1.6 A

65 kA

2 x M25

HCS1P 252616 S01261

1.6 – 2.5 A

65 kA

2 x M25

HCS1P 252616 S01271

2.5 – 4 A

65 kA

2 x M25

HCS1P 252616 S01281

4 – 6.3 A

16 kA

2 x M25

HCS1P 252616 S01291

6.3 – 10 A

16 kA

2 x M25

HCS1P 252616 S01301

10 – 16 A

16 kA

2 x M25

HCS1P 252616 S01311

16 – 20 A

12 kA

2 x M32

HCS1P 252616 S01321

20 – 25 A

12 kA

2 x M32

HCS1P 252616 S01331

Undervoltage trip (U)

As an option, motor circuit breakers intended for use in hazardous areas can be fitted with an undervoltage trip, the purpose of which is to automatically switch off the device if the supply voltage falls below a safe level. This protects both the motor itself and other plant components from the effects of unstable power supply conditions. Importantly, the switch prevents the motor from restarting automatically when the voltage returns, which is important for safety in Ex zones.

Trip characteristics for overloads

The graph shows the dependence of the tripping time on the current value (expressed as a multiple of the rated current In) at an ambient temperature of 30°C. This characteristic provides an effective response for both light and heavy overloads:

for high overloads (e.g. 8-10 ×In) – in milliseconds,

for low overloads (1.2-2 ×In), the response occurs after a few minutes or so.

Motor circuit breakers for explosive atmospheres

HARDO motor circuit breakers of the HCS1P series are designed for operation in potentially explosive atmospheres, in zones 1, 2, 21 and 22. Their primary type of protection in the context of explosion safety is Ex e protection (i.e. reinforced construction). In addition, Ex HARDO motor circuit breakers have overload protection and can be equipped with undercurrent protection and auxiliary contacts (1NO + 1NC)

The Ex HCS1P motor circuit breakers are characterised by their high rated switching and breaking capacity – up to 65 kA, which ensures effective operation even in installations with high short-circuit energy. For motor control in category AC3, the device can handle loads up to 440 V / 25 A.

The diagram shows the basic connections of the main circuits (L1, L2, L3 – T1, T2, T3), the undervoltage trip control circuit and the auxiliary contacts (13-14 and 21-22). When voltage is applied and the circuit is activated, the motor is switched on. In the event of an overload or voltage drop, the trip mechanism disconnects the power supply. The operating contact category is AC-3

The main terminals are suitable for conductors with a cross-section of 1 to 10 mm² (or 6-10 mm² when using collets), allowing flexible adaptation to different installations.

electrical diagram of the Ex HARDO motor circuit breaker

Ex motor circuit breakers may include auxiliary contacts (one NO and one NC) which are independent of the main tracks and can be used for:

transmission of the circuit-breaker operating status signal to a higher-level system (e.g. PLC),

activation of optical or audible signalling,

blocking the start-up of other devices in the system.

The category of auxiliary contacts is AC15 (1 A/230 V). The terminals for the auxiliary contacts allow the connection of wires with a cross-section of 1 to 2.5 mm².

The motor circuit breaker housing for hazardous areas is made of unsaturated polyester resin. Reinforced with glass fibre and mineral fillers, the housing does not melt, drip, or emit excessive smoke in the event of a fire. The product does not contain halogens, heavy metals or any substances listed on the REACH SVHC list.

The housing provides high mechanical and chemical resistance.

The outer casing material has additives to reduce electrification, which negates the risk of ignition of explosive atmospheres due to electrostatic discharge.

ATEX Directive requirements for motor connectors

Electric motors used in potentially explosive atmospheres require special protection against overloads and short circuits, as required by the ATEX Directive (2014/34/EU) and the IEC 60079-14 and EN 60079-0 standards.

Overloads and short circuits can lead to excessive heating of the motor windings, damage to the insulation, as well as arcing and sparking. In the presence of explosive mixtures (gases, flammable liquid vapours or dust), this can lead to an ignition of an explosive atmosphere.

Any electrical equipment operating in a hazardous area must be designed, selected and installed taking into account the specific requirements resulting from the Ex-zone classification and the equipment category.

The entire drive system must comply with the temperature class requirements (e.g. T3, T4) and be appropriately sized for the type of zone (0, 1, 2 for gases or 20, 21, 22 for dusts) and explosion group.

These protection measures effectively reduce ignition risk, ensuring safe, reliable, and compliant operation of electric drives in explosive atmospheres.